Transformer Oil: Restored to IEC Compliance in Two Passes

Transformer oil purification in two passes: breakdown voltage from 14 kV to 70 kV and water from 350 to 28 mg/kg.

Electrical substation transformers with high-voltage bushings at sunset
case study

How offline filtration restored non-serviceable transformer insulating oil

The Challenge

A transformer oil service company supplied a batch of aged, service-withdrawn mineral insulating oil for a controlled trial at Delta-Xero's UK facility. The oil was non-serviceable under both BS 148:2020 and IEC 60422:2013.

Water content was 350 mg/kg, more than eight times the 40 mg/kg limit, and breakdown voltage (BDV) had fallen to 14 kV, less than half the 30 kV minimum. Sediment was present, resistivity at 90°C was just 3.57 GΩm and the dissipation factor was 0.0774, all pointing to ionic and polar contamination with a risk of partial discharge and dielectric failure.

The Solution

The oil was processed through a Delta-Xero DX1001T portable offline kidney-loop unit fitted with a single filter cartridge, designed to remove particulate, dissolved moisture, sludge and carbonaceous material without draining or disconnecting the host system.

Two complete passes by volume were run in an open-barrel configuration, with continuous exposure to ambient moisture and dust, so the results are a conservative baseline. Samples taken before filtration, mid-pass 1, end of pass 1 and end of pass 2 were tested independently by VPS Power Ltd (UKAS accredited) under IEC 60247, IEC 60156, IEC 60814 and LP 7300.

The Results

  • Water down 92%: from 350 mg/kg to 34 mg/kg in the first pass, below the BS 148:2020 limit, and 28 mg/kg after the second.

  • Breakdown voltage up 400%: from 14 kV to 45 kV in pass one and 70 kV after pass two, 133% above the 30 kV minimum.

  • Resistivity restored: from 3.57 GΩm to 14.58 GΩm.

  • Clear and bright: visible sediment cleared within the first pass.

  • IEC 60422:2013 compliance: all filtration-addressable parameters assessed satisfactory for continued in-service use.

Parameter

Before

After pass 2

Water content

350 mg/kg

28 mg/kg

Breakdown voltage

14 kV

70 kV

Resistivity at 90°C

3.57 GΩm

14.58 GΩm

Visual condition

Sediment present

Clear and bright

Sealed in-service transformer systems would be expected to perform better than this open-barrel trial. Download the full transformer oil case study for the laboratory data.

Related Case Studies

About us - Delta-xero

Reduced iron levels and lower PQ index

A 1.5 MW wind turbine gearbox showed persistent contamination risk despite routine oil analysis. To understand the true internal condition of the gearbox, debris captured inside an offline filtration unit was analysed after extended in-service operation. Standard oil samples alone were not showing the full extent of varnish, wear debris, and moisture present within the system.  

View Case Study
Off-shore Oil and Gas: Case Study 2

The Additive Myth Debunked

A long-term independent study was carried out by POLARIS Laboratories Europe to assess whether installing Delta-Xero filtration on a landfill gas engine would negatively affect lubricant condition, additive performance, or expected oil drain intervals.

View Case Study
contact us

Ready to transform your oil management?