The Challenge
A transformer oil service company supplied a batch of aged, service-withdrawn mineral insulating oil for a controlled trial at Delta-Xero's UK facility. The oil was non-serviceable under both BS 148:2020 and IEC 60422:2013.
Water content was 350 mg/kg, more than eight times the 40 mg/kg limit, and breakdown voltage (BDV) had fallen to 14 kV, less than half the 30 kV minimum. Sediment was present, resistivity at 90°C was just 3.57 GΩm and the dissipation factor was 0.0774, all pointing to ionic and polar contamination with a risk of partial discharge and dielectric failure.
The Solution
The oil was processed through a Delta-Xero DX1001T portable offline kidney-loop unit fitted with a single filter cartridge, designed to remove particulate, dissolved moisture, sludge and carbonaceous material without draining or disconnecting the host system.
Two complete passes by volume were run in an open-barrel configuration, with continuous exposure to ambient moisture and dust, so the results are a conservative baseline. Samples taken before filtration, mid-pass 1, end of pass 1 and end of pass 2 were tested independently by VPS Power Ltd (UKAS accredited) under IEC 60247, IEC 60156, IEC 60814 and LP 7300.
The Results
Water down 92%: from 350 mg/kg to 34 mg/kg in the first pass, below the BS 148:2020 limit, and 28 mg/kg after the second.
Breakdown voltage up 400%: from 14 kV to 45 kV in pass one and 70 kV after pass two, 133% above the 30 kV minimum.
Resistivity restored: from 3.57 GΩm to 14.58 GΩm.
Clear and bright: visible sediment cleared within the first pass.
IEC 60422:2013 compliance: all filtration-addressable parameters assessed satisfactory for continued in-service use.
Parameter | Before | After pass 2 |
|---|
Water content | 350 mg/kg | 28 mg/kg |
Breakdown voltage | 14 kV | 70 kV |
Resistivity at 90°C | 3.57 GΩm | 14.58 GΩm |
Visual condition | Sediment present | Clear and bright |
Sealed in-service transformer systems would be expected to perform better than this open-barrel trial. Download the full transformer oil case study for the laboratory data.