Aerial view of bulk fuel storage tanks at a port

Portico Bulk Diesel Tank: Fuel Polishing That Keeps Up With Top-Ups

Continuous diesel fuel polishing on a 22,000 litre port tank: ISO 20/19/19 to 16/14/11, top-up after top-up.

Aerial view of bulk fuel storage tanks at a port
case study

Why continuous fuel polishing beat one-off diesel tank cleaning at a busy port

The Challenge

Portico Shipping’s 22,000 litre diesel tank at Portsmouth International Port operates 24 hours a day and is refilled approximately every two weeks, supplying fuel to mobile cargo-handling equipment. Laboratory analysis showed critical fuel cleanliness of ISO 20/19/19, putting injectors, pumps, equipment reliability and emissions performance at risk.

Because fresh deliveries were regularly mixed into the existing stock, Portico needed continuous treatment that would maintain cleanliness after every top-up rather than a one-off tank clean or fuel polishing exercise.

The Solution

A Delta-Xero DX1003-T-M was installed directly on the tank in a continuous offline loop, removing fine particulate and moisture before returning conditioned fuel to storage. An MP Filtri ICM 2 particle counter provided live ISO cleanliness and relative humidity readings, and laboratory samples independently verified the improvement.

The Results

  • Diesel target beaten: laboratory cleanliness improved from ISO 20/19/19 to 16/14/11, against a target of 18/16/13.

  • Large particles: particles larger than 14 µm fell by about 99.6%, from 2,787 to 12 per mL.

  • Fine particles: particles larger than 4 µm fell by about 94.4%, from 9,793 to 544 per mL.

  • Live monitoring: the online counter recorded ISO 11/9/6.

  • Sustained control: continuous filtration keeps the fuel clean after routine deliveries.

Parameter

Before

After

Target

Change

ISO code

20/19/19

16/14/11

18/16/13

Target exceeded

>4 µm /mL

9,793

544

2,500 max

94.4% lower

>6 µm /mL

4,971

152

640 max

96.9% lower

>14 µm /mL

2,787

12

80 max

99.6% lower

Water

61 ppm

48 ppm

–

21.3% lower

Download the full Portico bulk diesel tank case study for the complete fuel analysis.

Related Case Studies

About us - Delta-xero

Reduced iron levels and lower PQ index

A 1.5 MW wind turbine gearbox showed persistent contamination risk despite routine oil analysis. To understand the true internal condition of the gearbox, debris captured inside an offline filtration unit was analysed after extended in-service operation. Standard oil samples alone were not showing the full extent of varnish, wear debris, and moisture present within the system.  

View Case Study
Off-shore Oil and Gas: Case Study 2

The Additive Myth Debunked

A long-term independent study was carried out by POLARIS Laboratories Europe to assess whether installing Delta-Xero filtration on a landfill gas engine would negatively affect lubricant condition, additive performance, or expected oil drain intervals.

View Case Study
contact us

Ready to transform your oil management?