Fuel Oil for Ferries: From Too Dirty to Measure to ISO 16/14/11

The challenge

A ferry operator was concerned about the cleanliness of the fuel oil feeding its fleet, both as delivered by its supplier to the bunker barge and as delivered from the barge to the ferries. Independent lab analysis showed the delivered fuel at ISO 20/18/12, above both the ISO 4406 minimum and the engine manufacturer's recommended limit of 18/16/13, with 7,274 particles/mL at ≥4 µm against a limit of 2,500. The fuel in the bunker barge tank was worse: contamination inside the tank was mixing with the delivered fuel, and there was so much of it that the lab could not produce a meaningful reading. As part of a Delta-Xero fuel cleanliness assessment, a sample of the barge fuel was filtered and its condition independently monitored and verified.

Customer savings & impact

Following filtration with a Delta-Xero DX-1001-T-PT system fitted with an inline particle counter, the fuel showed clear, measurable improvements:

  • Cleanliness improved from ISO 24/23/22 to 14/13/12 in just 25 minutes of filtering

  • Independent lab verification at ISO 16/14/11, well within the engine manufacturer's 18/16/13 limit, with ≥4 µm particles down to 434/mL against a limit of 2,500

  • Fuel returned from a critically contaminated state to well within ISO 4406 and engine manufacturer standards, supporting a longer mean time between failures, less downtime and lower O&M costs

The full case study shows how contamination levels fell during filtering, what ISO improvements were independently verified, and how continued filtration can clean the bunker barge tank itself, removing the need for tank flushing and eliminating diesel bug.

Related Case Studies

Offshore oil and gas drilling platform at sea

Slashing MPC Values by 85%

An offshore drilling platform in the offshore oil & gas industry experienced recurring reliability issues within its compressor lubrication system

View Case Study
Pneumatically driven ATEX Zone 1 oil management system for anaerobic digester pump and valve actuators

Silicon Removal

This case study shows how Delta-Xero tested landfill gas engines, including CAT 3516, CAT 3520, Jenbacher 320 and Jenbacher 420, to prove that silicon levels alone do not accurately show how harmful the contamination really is. It uses POLARIS lab analysis and Micro Patch Ferrography to reveal abrasive wear, varnish and contamination that standard oil analysis can miss. It also shows before/after examples where Delta-Xero reduced abrasive contamination by around 98% and helped extend oil drain intervals.

View Case Study
contact us

Ready to transform your oil management?